Review of High Relative Humidity in Catheter Laboratory of a Private Hospital and a Low Energy Consuming Solution

Authors

  • Jaya Prathab T. Arumugam Faculty of Arts & Science, International University of Malaya-Wales, Kuala Lumpur, Malaysia Author
  • Kamran Shavarebi Associate Professor, Faculty of Arts & Science, International University of Malaya-Wales, Kuala Lumpur, Malaysia Author

DOI:

https://doi.org/10.34256/irjmt2122

Keywords:

Dry Bulb, Wet Bulb, Moisture, Relative Humidity, Energy

Abstract

The Relative Humidity in a Catheter Laboratory is desirous to be controlled within a range of 30 to 65% RH. A maximum Relative Humidity (RH) fluctuation of up to 70% is tolerated. A case study is presented whereby a high RH of up to 80% RH has been recorded in the examination room of a Catheter Laboratory (CathLab) in a local Hospital. The conditioned air to the CathLab is supplied through an existing dedicated Chilled Water Air Handling Unit. Two (2) solutions were considered and the technical and commercial comparisons carried out. The first option is an inline dehumidifier system and the second option is to install a portable standalone dehumidifier inside the CathLab examination room. Solutions to address the high Relative Humidity have to be carefully considered as the introduction of in-line dehumidifiers contribute to higher energy consumption. The latter was selected based on commercial reasons. Three (3) weeks of RH monitoring via the building’s Integrated Building Management System (IBMS) was carried out. The readings measured show a drastic reduction in RH to a mean of about 60% RH which meets the end user’s requirement. The cost for the second option was also found to be much lower at about 10% of the first option.

References

Engineering Services Division, Guideline on Mould Control and Remediation in Healthcare Facilities. (2016).

https://www.scribd.com/document/386978214/HtfQuGuideline-on-Mould-Control-Remediation-In-Healthcare-Facilities-October-2016-pdf Accessed on December 2020.

K. Aini Mohd Sari, K. Farhah Almar Mastaza, M. Ashraf Abdul Rahman, N. Saji, R. Muslim, M. Syafiq Syazwan Mustafa, & T. Yean Ghing, Assessment of indoor air quality parameters at Ambulatory Care Centre XYZ, Malaysia, IOP Conference Series: Earth and Environmental Science, 373(1) (2019). https://doi.org/10.1088/1755-1315/373/1/012013

C.W. Callahan, A.M. Elansari, & D.L. Fenton, (2019). Psychrometrics. In Postharvest Technology of Perishable Horticultural Commodities (pp. 271–310). https://doi.org/10.1016/B978-0-12-813276-0.00008-0

S. Sattayakorn, M. Ichinose, & R. Sasaki, Clarifying thermal comfort of healthcare occupants in tropical region: A case of indoor environment in Thai hospitals, Energy and Buildings, 149 (2017) 45–57. https://doi.org/10.1016/j.enbuild.2017.05.025

Fouras, M.J. Kitchen, S. Dubsky, R.A. Lewis, S.B. Hooper, & K. Hourigan, The past, present, and future of x-ray technology for in vivo imaging of function and form, Journal of Applied Physics, 105(10) (2009). https://doi.org/10.1063/1.3115643

D. Meyer, & D. Thevenard, PsychroLib: a library of psychrometric functions to calculate thermodynamic properties of air, Journal of Open Source Software, 4(33) (2019) 1137. https://doi.org/10.21105/joss.01137

M. Ahmadzadehtalatapeh, & Y. H. Yau, Assessment of climate change impact on the required cooling load of the hospital buildings, Journal of Engineering Science and Technology, 12(8) (2017) 2091–2105.

H. Ren, Construction of a Generalized Psychrometric Chart for Different Pressures, International Journal of Mechanical Engineering Education, 32(3) (2004) 212-222. https://doi.org/10.7227/IJMEE.32.3.3

M.H. Mahmood, M. Sultan, & T. Miyazaki, Solid desiccant dehumidification-based air-conditioning system for agricultural storage application: Theory and experiments, Proceedings of the Institution of Mechanical Engineers, Part A: Journal of Power and Energy, 234(4) (2020) 534–547. https://doi.org/10.1177/0957650919869503

Purushothama, (2009). Humidification and Ventilation Management in Textile Industry, Elsevier.

N.C. Burton, Evaluation of Indoor Environmental Quality Concerns Among Hospital Employees Working in a Radiology Department. NIOSH health hazard evaluation report, (2018). https://stacks.cdc.gov/view/cdc/76247 Accessed on December 2020.

I.S. Kurniawansyah, M. Abdassah, & S. Gondodiputro, Relationship between Temperature and Humidity on Sterility of Reusable Instruments in Hospital’s CSSD, International Journal of Pharmaceutical Sciences Review and Research, 33(2) (2015) 215–219.

Downloads

Published

2021-03-01

How to Cite

T. Arumugam, J.P. and Shavarebi, K. (2021) “Review of High Relative Humidity in Catheter Laboratory of a Private Hospital and a Low Energy Consuming Solution”, International Research Journal of Multidisciplinary Technovation, 3(2), pp. 7–13. doi:10.34256/irjmt2122.